The Anord Mardix Modular Circuit Monitoring System (MCMS) has been redefining circuit monitoring since its introduction with a single unit monitoring up to 96 circuits (32 x 3 phase). MCMS is an economical solution for monitoring new installations but it is also designed for retrofit and is small enough to fit inside existing panels.
MCMS technology from Anord Mardix simplifies installation and connectivity while providing instant access to data in a user-friendly format. The versatile Core Module™ system is a single monitoring solution with peripherals that are optimised for branch circuit and multi-circuit monitoring applications.




Input power (standard) 90-277 VAC (480 VAC 4W+G) 50/ 60 Hz
Input power (enhanced) 480-600 VAC (3W or 4W+G) 50/ 60 Hz
Voltage connection terminals 22 – 14mm/sq.
Overload protection Internally fused
Power consumption <5W / 0.1 A @ 240 VAC Channels / circuit capacity 24 x 4 channels (96 circuits total) PERFORMANCE Accuracy 0.50% Sampling rate > 3 kHz
Data protocols Modbus TCP/IP (Ethernet), Modbus RTU (RS-485 2 wire), HTML (web server), SNMP and BACnet.
Modbus serial specifications 9600, 19200, 38400 Baud (selectable)
Ethernet ports 2 x RJ-45 10/100 Mbit
USB port USB 2.0 Type A
Web server HTML via standard browser
WiFi option 802.11 g/n ; requires WiFi option
Operating temperature 0 to 60 °C (32 to 140 °F) (<95% RH non-condensing)
Storage temperature -40 to 70 °C (-40 to 158 °F)
Enclosure versions NEMA 1/IP20 (indoor use); NEMA 4 / IP67 (outdoor use)
Agency approvals UL Listed to EN61010-1, Cat. III, pollution degree 2, CE
The versatile and compact Core Module™ functions as a gateway that can host up to four interface modules monitoring a total of 96 circuits. Interface modules connect via ethernet cables and are available for new and retrofit branch circuit and multi-circuit applications. Further accessories are available to enable monitoring of direct current voltages at the final circuit level
Purpose built, application-specific Interface Boards simplify installation using intuitive form factors and simplified connectivity via Ethernet cable.
Optional presence of v or breaker status per circuit
24 CTs / circuits per module (96 Total)
Supports 0.33 V solid core and split core CTs as well as available native Rogowski coil version available
Contact us to discuss your project, or you can view more documentation and our MCMS datasheets.